Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/29/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The three existing rooftop units (two 4-ton units and one 5-ton unit) serving the warehouse share a common return with a combined design capacity greater than 2,000 CFM and require smoke detectors. Provide smoke detectors in the return air ducts of the three units, upstream of any outside air connections. Reference: Section 606.2.2, IMC 2018, as amended by the City of Tucson.
06/29/2022 ROBERT SHERRY WATER REVIEW Completed
07/09/2022 JVINCEN1 FIRE REVIEW Approved
07/13/2022 STEVE SHIELDS ZONING REVIEW Approved
07/13/2022 SSHIELD1 ENGINEERING REVIEW Passed
07/13/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/13/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/26/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed