Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM04645
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/29/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/29/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The three existing rooftop units (two 4-ton units and one 5-ton unit) serving the warehouse share a common return with a combined design capacity greater than 2,000 CFM and require smoke detectors. Provide smoke detectors in the return air ducts of the three units, upstream of any outside air connections. Reference: Section 606.2.2, IMC 2018, as amended by the City of Tucson. |
| 06/29/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/09/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 07/13/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 07/13/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 07/13/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/13/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/26/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Completed |