Permit Number: T22CM04611
Parcel: 133102510

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM04611
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2022 PCAMARE1 ENGINEERING REVIEW Passed
07/01/2022 STEVE SHIELDS ZONING REVIEW Passed
07/12/2022 AWARNER1 NPPO REVIEW Approv-Cond Native plants are to preserved in place, or if removed, replaced with another native tree. Sections 7.7.3.D.3 & .4 of the Unified Development Code (UDC) and Admin. Manual Section 2-11.0.0
07/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04611


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Denied
1. Indicate the approximate location of the electrical line to be run form the house to the new garage on the site plan. Indicate the type of material (such as direct burial, PVC conduit) and its burial depth on the plans.
2. Note on the drawings that the garage will be provided with a separate means of disconnect. A disconnecting means for all conductors is required for the detached garage that is readily accessible and near the point of entrance. 2017 NEC 225.31.
3. Indicate all 15- and 20-amp outlets shall be tamper proof type. 2017 NEC 210.52.
4. Indicate GFCI protection will be provided for all receptacles located in the garage. 2017 NEC 210.8 (B).


PLUMBING REVIEW COMMENTS:
Conditionally Approved
No plumbing was indicated as part of this submittal



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov