Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2022 ROBERT SHERRY WATER REVIEW Completed
07/13/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments
07/13/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04606

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1. Please provide a COMcheck that indicates compliance for new mechanical system and scan that data onto one of the mechanical sheets. This provides evidence the mechanical system is in compliance.


ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/13/2022 STEVE SHIELDS ZONING REVIEW Reqs Change Until T22CM02962 is approved Zoning cannot approve this TI
07/13/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
07/14/2022 JPEELDA1 FIRE REVIEW Approved