Permit Number: T22CM04602
Parcel: 10409218A

Address:
4151 N ORACLE RD

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM04602
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide site lighting plans showing complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. See section 104 for plan submittal requirements Provide evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

Provide site lighting plans with the following information on the plans;

Provide a complete luminaire schedule.

Size of the parcel in acres.

See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing.

(d) 402.1 (light source color temperature requirements), shielding requirements, etc .

(e) Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1.

(f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

(g) Specify any exceptions used.

(h) Curfew lighting controls If applicable.

Do not confuse the Outdoor Lighting Code with the IECC.

Provide complete compliance with the 2018 IECC for interior and exterior lighting modifications where applicable.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/14/2022 VVERA1 OUT TO CUSTOMER Completed