| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/18/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comment and provide a written response. 1. The electrical site/floor plan utility secondary feeders does not correlate with the electrical line diagram. 2. Show conductor quantities, sizes and types for the service secondary feeders. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/19/2022 | VVERA1 | OUT TO CUSTOMER | Completed |