Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM04586
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/28/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
06/28/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
07/05/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM04586 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Include the proposed live and dead loads for the new structure on the drawings. 2. Indicate that new construction has been designed to withstand a minimum wind speed of 115 mph and Seismic Zone B. 2018 IRC R301.2(1). 3. Provide a detail on how the new foundation and slab will connect to the existing building foundation and existing pergola. 4. Update the truss notes on sheet 3 to indicate the truss drawings will be provided as a deferred submittal prior to rough inspections. BUILDING REVIEW COMMENTS: Denied 1. The site plan indicates the existing pergola is being reduced to 300 sf. clarify if there will be work in this area and if so, show it on the plans. 2. Note on the plans that attic venting will be provided in accordance with 2018 IRC R806. 3. Note on the plans that fire blocking will be installed in all walls and concealed spaces prior to covering. 2018 IRC R302.11. 4. Note on the plans the energy requirements for the new windows. A maximum U factor of 0.40 is required with a maximum SHGC of 0.25. MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Denied 1. Indicate smoke detectors shall be installed in each sleeping room, outside of each sleeping room in the immediate vicinity of the bedroom. 2018 IRC R314.2. Note on the drawings that all smoke detectors shall be hard wired with a battery backup and shall be interconnected so that the actuation of one alarm will activate all. 2018 IRC R314.4. 2. Indicate carbon monoxide detectors shall be installed outside of each sleeping area in the immediate vicinity of the bedrooms including in the existing house. 2018 IRC R315.3. Note on the drawings that carbon monoxide devices shall be hard wired with a battery backup and shall be interconnected so that the actuation of one alarm will activate all. 2018 IRC R314.4. Smoke detectors and carbon monoxide alarms may be combined. PLUMBING REVIEW COMMENTS: Conditionally Approved No plumbing work as part of this submittal If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
07/15/2022 | AWARNER1 | NPPO | REVIEW | Approved |