| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/24/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 08/25/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 08/25/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | DRAWINGS REVISED TO DIRECT HAND SINK & FLOOR SINK TO GREASE WASTE. Floor sinks in the kitchen shall discharge through a grease interceptor. Hand sinks (SK-1) in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson. [Initial comment: The new 3-compartment sink, hand sink, and floor sink in the expansion area do not discharge to grease waste. What operations are happening with these fixtures? Reference: Section 1003.1, IPC 2018.] |