Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM04575
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/29/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The Plumbing Fixtures Schedule shows kitchen fixture mark #3 as a "walk-in condenser coil"; is this actually the evaporator coil for the walk-in? Reference: Section 107.2.1, IBC 2018. 2. The new 3-compartment sink, hand sink, and floor sink in the expansion area do not discharge to grease waste. What operations are happening with these fixtures? Reference: Section 1003.1, IPC 2018. |
| 06/29/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide calculations to verify that adequate ventilation will be provided for the expansion area. Reference: Section 403.3.1.1, IMC 2018. |
| 06/29/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/09/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 07/12/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 07/12/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 07/12/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please use the current 2018 IECC for the energy lighting calculations Comcheck. Ref; 2018 IECC |
| 07/12/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 08/11/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Activity Number: T22CM04575 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. BUILDING REVIEW COMMENTS: Denied Sheet A1.0 Provide site plan showing Accessible Parking and required path of travel to doors, parking and the Public Way. Per ICC A117 and Chapter 11 IBC. Sheet A2.0 Provide existing plan per Chapter 10 of the IBC. Sheet A2.0 Verify existing restroom comply with ICC A117 If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |