Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM04573
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/29/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide specifications for the proposed heat pumps. Show that the proposed replacement rooftop units meet the requirements of Section R403, IECC 2018. Reference: Section C501.4, International Energy Conservation Code 2018. 2. Provide the installed weight of the rooftop equipment. Provide structural calculations to verify that the roof framing is adequate to support the proposed mechanical units on the roof (e.g. point load as well as dead load). Provide structural details as required for any special framing revisions needed to support the units and frame the roof penetrations. Reference: Section 302.1, IMC 2018. 3. Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.11, IMC 2018. 4. Provide an electrical receptacle at or near the equipment location as required by NFPA 70. Reference: Section 306.5.2, IMC 2018 5. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson. 6. Provide calculations to verify that adequate ventilation will be provided for each apartment. Reference: Section 403.3.2, IMC 2018, and Section R403.6, IECC 2018. |
| 07/18/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Ref; Plan Sheet E-2. (a) Lighting Plan. The notes referring to the lighting are note legible due to overlapping of the notes. Provide compliance with the 2018 IECC and Tucson/Pima County Outdoor Lighting Code for the interior and exterior lighting. (b) Provide for Tamper resistant receptacle for replaced receptacles. NEC 201, Nec 406.12. Ref; Plan Sheet E-3. Show the electrical service riser conduit size, type, and also conductor quantities, sizes and types. NEC 230.42. The panel schedules load areas are blank. Provide complete panel schedules. Balance A and B loads as close as possible. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC) |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/18/2022 | VVERA1 | OUT TO CUSTOMER | Completed |