Permit Number: T22CM04552
Parcel: 134210040

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM04552
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04552

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide Structural Calculations for Foundations, Columns and Roof Framing per Section 1601.1 of International Building Code 2018.
2. Provide Wind Load Calculations for the Building per Section 1609 of International Building Code 2018.
3. Provide Seismic Calculations for the Building per Section 1613 of International Building Code 2018.
4. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.
5. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1.
6. Submit documentation regarding implementation of Special Inspections and Testing program during construction to observe compliance with the Design Concepts and Specifications.
7. Provide schedule of special inspections as required in IBC Section 1705.
8. DEFERRED SUBMITTAL REQUIREMENTS
Structural general notes are to include any components of the building that may be considered deferred submittals. IBC Section 107.3.4.1 requires deferred submittals to be approved by the building official.
If items will be deferred the plans are to clearly note the following per IBC Section 107.3.4.1:
* To be reviewed by design professional in responsible charge.
* Design professional shall affix a notation that the deferred items are in general conformance with their design of the building.
* They shall be submitted for review by the building official.
* Shall not be installed until approved by building official.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Denied
1. Sheet E.01 : Include date calculation was made for maximum available fault current at panelboard A and panelboard B. This is required for label to be made and placed at service . NEC 2017, 110.24
2. Sheet E.01: Show in single line location where the connection to the grounding electrode conductor shall be made. NEC 2017. 250.24(A)(1)
3. Sheet E1.1: Show ampere rating of roof RTU 1 and RTU 2 disconnects.
4. Sheet E1.1: Show conductor sizes for walk-in coolers / freezers circuits A(17), A(19, 21) and A (31, 33).


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). 2" Inch Hub drain beneath equipment item #62 needs to be connected to the grease system on plan pages P1.0 & P1.1
2). Primary & secondary roof drain conductors need to be illustrated within the plumbing plans to their discharge terminations as stated on detail #9 on plan page A6.0. Include sizing calculations & the GPM load to each set of conductors. -IPC 1106.1, 1106.2


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/07/2022 ROBERT SHERRY WATER REVIEW Completed
07/12/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM04552 – DP22-0151
4857 E Grant Rd – C-2
Food Service (1st Review)

TRANSMITTAL: July 12, 2022
This site is located in C-2 Zone (UDC 4.7.21), a Food Service use is an allowed use in the zone (UDC Table 4.8-4) subject to Use Specific Standard 4.9.4.M.1 and 4.9.13.P.

1. Zoning has reviewed the building plans for compliance with DP22-0151 and although it appears that the building plans match the DP, except for the comments below, Zoning cannot approve the building plan until the DP is approved.

2. The building height shown on the DP, 15.25’ does not match what is shown on the elevations in this building set.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/12/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/08/2022 JPEELDA1 FIRE REVIEW Approved
08/09/2022 KROBLES1 ENGINEERING REVIEW Needs Review until the DP is approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2022 KROBLES1 OUT TO CUSTOMER Completed