Permit Number: T22CM04515
Parcel: 131040630

Address:
4873 E 24TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM04515
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2022 WBERGER1 ZONING REVIEW Approved
06/21/2022 WBERGER1 NPPO REVIEW Passed
06/29/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04515

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. The listed adopted and applicable codes are incorrect. Provide a corrected list of adopted and applicable codes.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/13/2022 PCAMARE1 ENGINEERING REVIEW Reqs Change This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
• Is this for a new or existing activity application? – Please select New Application.

• Submission Type – Select Floodplain Use Permit.

• Project Name – Enter a name for your project.

• Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

• Type of Permit – Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

• Complete the Applicant Info.
• Complete the Contractor, Owner and Architect/Engineer sections as applicable.

• Supporting Documentation Upload – Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful.

• Sign the application and submit.

• You will be given an activity number for your submittal. Please copy and send this number back to us so we can continue the review.