Permit Number: T22CM04468
Parcel: 12810079B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM04468
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/28/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/28/2022 ROBERT SHERRY WATER REVIEW Completed
07/06/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Ref; Plan Sheet E2.0.

(a) The electrical floor plan shows the device branch circuit designated to panel ‘4LV’. This does not correlate with General Note #5. Please clarify.

(b) Show the designated breaker panel location on the electrical floor plan.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
07/09/2022 JVINCEN1 FIRE REVIEW Approved
07/11/2022 STEVE SHIELDS ZONING REVIEW Approved
07/11/2022 SSHIELD1 ENGINEERING REVIEW Passed
07/11/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/27/2022 JGARCIA1 BUILDING-COMMERCIAL REVIEW Completed