Permit Number: T22CM04440
Parcel: 106060140

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM04440
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/27/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/27/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide cleanouts for all horizontal drains and an additional cleanout for each 40-foot section of drains having a change of direction greater than 45 degrees. The cleanouts shall be sized per Section 708.1.7, IPC 2018 and shall open to allow cleaning in the direction of flow. Reference: Sections 708.1.1 and 708.1.8, IPC 2018.
2. Show the existing building drains to verify that the new combination drain and vent pipes are properly sized per Table 915.2.2, IPC 2018.
3. Verify if an existing grease interceptor is currently in place to prevent the discharge of fats, oil, and grease into the public sewer. If a grease interceptor is not in place, show how the public sewer is to be protected from harmful discharges. Reference: Section 1003.1, IPC 2018.
06/27/2022 ROBERT SHERRY WATER REVIEW Completed
06/30/2022 PCAMARE1 ENGINEERING REVIEW Passed
07/06/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Ref; Plan Sheet E3.

There is no existing load calculation shown for existing panel ‘D’. Just total service load per APS.

Perform load calculations for the 200 amp rated panel ‘D’ prior to adding the 75 amp load from new panel ‘K’. Measuring the load for panel ‘D’ after adding the load from new panel ‘K’ is not an approved code method. NEC art’s 215, 220, 240. See ‘ONE LINE KEYNOTE #2’. Or, provide an NEC code article that states measuring total load after adding new load to an existing AC system panelboard to verify it can support the load is an approved code method.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
07/08/2022 STEVE SHIELDS ZONING REVIEW Approved
07/08/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/21/2022 JVINCEN1 FIRE REVIEW Approved