Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T22CM04426
Parcel: 13631002S

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM04426
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04426


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Sheet 1.0 – Show partial demolitions of floors to accommodate new foundations shown in Sheet 3.1 Foundation plan.
Sheet 1.1 – Provide dimensions of new concrete slab (keynote 18). Provide new 4” slab detail. Show slope drain direction (keynote 21).


BUILDING REVIEW COMMENTS:
Denied
Sheet 0.0 – Applicable code should include: ICC A117.1 - 2009 Accessible and Usable Buildings and Facilities (by reference)
Sheet 0.0 – Is signage part of differed submission?
Sheet 0.0 – Provide complete life safety/exit plan. Show portable fire extinguisher locations, exit lights, required, and provided exit travel distances and directions, and required and provided common path of travel per 2018 IBC chapter 10.
Sheet 0.0 – Provide fire alarm system scope.
Sheet 1.1 – Provide dimensions of new concrete slab (keynote 18). Provide new 4” slab detail. Show slope drain direction (keynote 21).
Sheet 1.2 – Provide guard rail per 2018 IBC section 1015. Section 1015.3 requires 42” min. height while exterior elevation showing at 36”. 4 inches opening limitations per section 1015.4.
Sheet 1.2 – Provide stair handrails per 2018 IBC 1014. Provide stair riser, tread, and nosing dimensions 7/sheet 1.7. Stair 8/Sheet 3.2 refers to Arch for dimensions.
Sheet 1.3 – Specify new exterior wall insulation R values. Wall detail 1/Sheet 3.2 does not specify R value.
Sheet 1.4 – Provide roof access location and method per 2018 IMC 306 (access and service space).
Sheet 1.4 – Show roof appliance distance to the roof edge. Do they require guards per 2018 IMC 304.11?
Sheet 1.4 – Provide and cross reference roof details such as eave and penetration details. Provide architectural details for sheet 5.2 (only structural shown).
Sheet 1.4 – Show distance between exhaust (keynote 4) and mechanical air intake (keynote 7). Do they meet over 10 feet per 2018 IMC section 501.3.1?
Sheet 1.6 – Label all room identifications, Typ. Bar, kitchen, prep., walk-in cooler, etc.
Sheet 1.6 – Identify the accessible counter and seating locations per 2018 IBC section 1108.2.9.1.
Sheet 1.7 – Provide interior floor finish details. Do they meet 2009 ICC A117.1 chapter 3 building blocks?


MECHANICAL REVIEW COMMENTS:
Denied
Sheet M3 – Does AA return provide smoke detector per City of Tucson Amendment 2018 IMC section 606.2.1? Show CFM.
Sheet M4 – “2012” IMC is referenced. City of Tucson Amendment 2018 IMC is the applicable code.



ELECTRICAL REVIEW COMMENTS
Denied
Sheet E-3 – Provide total outdoor light output per City of Tucson/Pima County Outdoor Lighting Code.
Sheet E-5 – “2016” IECC used for interior lighting code calculation while applicable code is City of Tucson Amendment 2018 IECC.


PLUMBING REVIEW COMMENTS:
Denied
Sheet P0 – What is the scope hole left after removing existing grease trap (keyed notes 2)?


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/29/2022 ROBERT SHERRY WATER REVIEW Completed
07/05/2022 STEVE SHIELDS ZONING REVIEW Approved
07/05/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/21/2022 JVINCEN1 FIRE REVIEW Reqs Change Denied

Sheet 0.0 – Provide complete life safety/exit plan. Show portable fire extinguisher locations, exit lights, required, and provided exit travel distances and directions, and required and provided common path of travel per 2018 IBC chapter 10.
Sheet 0.0 – Provide fire alarm system scope.
Sheet 1.6 – Label all room identifications, Typ. Bar, kitchen, prep., walk-in cooler, etc.

john.vincent@tucsonaz.gov
5203495581
08/09/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change 1. The Site plan needs to match what is being proposed on the approved Development Package. Keynote 18 - 4" Concrete Slab on sheet 1.1 is not shown on DP18-0204. Revise as necessary.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2022 VVERA1 OUT TO CUSTOMER Completed