Permit Number: T22CM04318
Parcel: 141411530

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM04318
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2022 RPARSON1 OIP REVIEW Completed
08/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04318

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide a lag bolt connection up-lift calculation demonstrating the wind load supporting capability R301.1
2. Provide sufficient standoffs for achieving a point load calculation of under 45 lbs. Provide point load calculation R301.1

BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/22/2022 NGARCIA3 OUT TO CUSTOMER Completed