Permit Number: T22CM04313
Parcel: 133030890

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM04313
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2022 RPARSON1 OIP REVIEW Completed
08/30/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04313

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide a lag bolt connection up-lift calculation demonstration the wind load supporting capability (115 MPH) per R301.1
2. Provide calculation showing sufficient standoffs to achieve point load calculation under 45 lbs R301.1


BUILDING REVIEW COMMENTS:
Approved
Installation of new PV system with 24 modules and associated equipment approved


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Denied
1. Provide locations for all markings (labels) required by NEC 690


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/30/2022 NGARCIA3 OUT TO CUSTOMER Completed