Permit Number: T22CM04242
Parcel: 141019260

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM04242
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2022 JPEELDA1 FIRE REVIEW Approved
08/23/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change See the definition of "private" in Section 202, IPC 2018. The two proposed restrooms are not private. Revise the hot water recirculation loop to limit the branch from the loop to 24" for a 1/2" branch or 6" for a ¾" branch. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]
09/07/2022 JGARCIA1 BUILDING-COMMERCIAL REVIEW Completed