Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM04242
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/16/2022 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 08/23/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | See the definition of "private" in Section 202, IPC 2018. The two proposed restrooms are not private. Revise the hot water recirculation loop to limit the branch from the loop to 24" for a 1/2" branch or 6" for a ¾" branch. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] |
| 09/07/2022 | JGARCIA1 | BUILDING-COMMERCIAL | REVIEW | Completed |