Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM04242
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/07/2022 | VFLORES1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Reqs Change | Please provide a unit # needs to be assigned prior to issuance. You may contact Pima County addressing ph# 520-724-9512 Email: Addressing@pima.gov |
| 06/20/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Cover: The title indicates this is a 90% set. Please provide the finished set of drawings for review. |
| 06/21/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/21/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. |
| 06/22/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 06/27/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/29/2022 | WBERGER1 | ENGINEERING | REVIEW | Passed | |
| 06/29/2022 | WBERGER1 | ZONING | REVIEW | Approved | |
| 06/29/2022 | WBERGER1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/18/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Distance shall be shown on the egress plan Occupant load shall be noted on the cover sheet Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner |