Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM04234
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM04234
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2022 JPEELDA1 FIRE REVIEW Approved
08/23/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/23/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Condensate drains may not terminate over a roof drain unless the roof drain itself terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Verify the termination of the roof drain. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson. [Initial comment: Show the size, routing, and termination of the condensate drain for RTU-3. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.]
08/30/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved