Permit Number: T22CM04234
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM04234
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2022 VFLORES1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change Please provide a unit # needs to be assigned prior to issuance. You may contact Pima County addressing ph# 520-724-9512 Email: Addressing@pima.gov
06/20/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/21/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
2. Show the size, routing, and termination of the condensate drain for RTU-3. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.
06/21/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
2. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
06/21/2022 ROBERT SHERRY WATER REVIEW Completed
06/23/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Show designated branch circuits and panels for all electrical devices, luminaires, mechanical equipment on the power and lighting plans. NEC 408.4

Indicate whether the loadcenters are new or existing and also any electrical appliances or equipment.

Provide full compliance with the 2018 IECC for the lighting.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
06/29/2022 WBERGER1 ENGINEERING REVIEW Passed
06/29/2022 WBERGER1 ZONING REVIEW Approved
06/29/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/18/2022 JPEELDA1 FIRE REVIEW Reqs Change Sheet G001 shows that the building has fire sprinklers but sheet G002 states that non are provided please clarify.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner