Review Details: COMMERCIAL - TI
Permit Number - T22CM04213
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/18/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1; Floor Plan: Per the IBC Section 903.2.3(2), an automatic sprinkler system is not required in a building where every classroom has not fewer than one exterior exit door at ground level. The room designated 'Child Care-4' does not meet that requirement. Please revise. |
| 06/20/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the calculation of the required minimum ventilation for HVAC units serving multiple zones using the balancing data (supply CFM) for each zone and the calculations described in Sections 403.3.1.1.2.3.1 through 403.3.1.1.2.3.4, IMC 2018. Reference: Section 403.3.1.1.2.3, IMC 2018. |
| 06/20/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that no additional plumbing fixtures will be required to obtain a day care license. Reference: Section 107.2.1, IBC 2018. |
| 06/20/2022 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Revise the site plan to show the location and size of the water meter. Verify that a reduced pressure backflow prevention assembly is present and show its location on the site drawing. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf |
| 06/23/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Add note requiring EM battery back-up and exit Lighting to be connected to a unswitched lighting branch circuit. Per NEC art 700. 2. Provide more detail as to the branch circuiting of the modified Fire Alarm System. NEC art 760. REf; 2918 IBC section 107.2.1, 2017 NEC |
| 06/29/2022 | PCAMARE1 | ENGINEERING | REVIEW | Passed | |
| 06/30/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T22CM04213 5820 S Nogales Hwy – R-2 Day Care Facility – Maximum 30 Children (1st Review) TRANSMITTAL: June 30, 2022 This site is located in R-2 Zone (UDC 4.7.9), Day Care - Child Care, maximum 30 children, is an use is an allowed use in the zone (UDC Table 4.8-2), subject to Use Specific Standards 4.9.4.H.1-5, .6.a & .7.d. 1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
| 06/30/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/15/2022 | JVINCEN1 | FIRE | REVIEW | Reqs Change | 1. Sheet A1; Floor Plan: Per the IFC Tucson Fire Amendments, Section 903.2.3, an automatic sprinkler system is not required in a building where every room used for instruction has at least one exit door directly to the outside at ground level. The room designated 'Child Care-4' does not meet that requirement. Please revise. Indicate the repair/update to the fire alarm will be a deferred submittal to Tucson Fire. |