Permit Number: T22CM04213
Parcel: 13810023A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM04213
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Floor Plan: Per the IBC Section 903.2.3(2), an automatic sprinkler system is not required in a building where every classroom has not fewer than one exterior exit door at ground level. The room designated 'Child Care-4' does not meet that requirement. Please revise.
06/20/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the calculation of the required minimum ventilation for HVAC units serving multiple zones using the balancing data (supply CFM) for each zone and the calculations described in Sections 403.3.1.1.2.3.1 through 403.3.1.1.2.3.4, IMC 2018. Reference: Section 403.3.1.1.2.3, IMC 2018.
06/20/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify that no additional plumbing fixtures will be required to obtain a day care license. Reference: Section 107.2.1, IBC 2018.
06/20/2022 ROBERT SHERRY WATER REVIEW Reqs Change Revise the site plan to show the location and size of the water meter. Verify that a reduced pressure backflow prevention assembly is present and show its location on the site drawing. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
06/23/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.
1. Add note requiring EM battery back-up and exit Lighting to be connected to a unswitched lighting branch circuit. Per NEC art 700.
2. Provide more detail as to the branch circuiting of the modified Fire Alarm System. NEC art 760.
REf; 2918 IBC section 107.2.1, 2017 NEC
06/29/2022 PCAMARE1 ENGINEERING REVIEW Passed
06/30/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM04213
5820 S Nogales Hwy – R-2
Day Care Facility – Maximum 30 Children (1st Review)

TRANSMITTAL: June 30, 2022
This site is located in R-2 Zone (UDC 4.7.9), Day Care - Child Care, maximum 30 children, is an use is an allowed use in the zone (UDC Table 4.8-2), subject to Use Specific Standards 4.9.4.H.1-5, .6.a & .7.d.

1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
06/30/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/15/2022 JVINCEN1 FIRE REVIEW Reqs Change 1. Sheet A1; Floor Plan: Per the IFC Tucson Fire Amendments, Section 903.2.3, an automatic sprinkler system is not required in a building where every room used for instruction has at least one exit door directly to the outside at ground level. The room designated 'Child Care-4' does not meet that requirement. Please revise.

Indicate the repair/update to the fire alarm will be a deferred submittal to Tucson Fire.