Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM04205
Parcel: 110113620

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM04205
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04205

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. General: Provide within the site plans, drawings that clearly indicate the accessible routes within the site and site arrival points that connect the accessible parking to the accessible entrances that are in accordance with Section 206.2.1 and 206.2.2. Additionally, ensure that accessible routes are maintained within the space.
2. General: Provide information regarding the adjacent tenants to ensure proper separation between tenants.
3. Sheet A010: The construction type is listed as III-B and exterior walls have no rating. In III-B construction the exterior walls have a 2 hour fire resistance fire rating. Provide clarification or correct the construction type.
4. Sheet A010: The construction type is listed as V-B under the allowable height box. It's listed differently in other locations. Provide the correct construction type used for this project.
5. Sheet A010: The egress plans are required to show all of the fixtures and equipment. Additionally, show the distance between the exits as required by Section 1006.2.1. Provide a revised and corrected egress plan.
6. Sheet A203: Provide the location of egress illumination on the RCP in accordance with Section 1008


MECHANICAL REVIEW COMMENTS:
Denied
1. Sheet M002: Provide the equipment schedule for all existing equipment.


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
1. General: The construction plans shall include for each floor level a riser diagram of the plumbing water and waste piping work. The construction plans shall indicate the direction of flow, all pipe sizes, grade of horizontal piping, loading, and location of fixtures and appliances. Please provide a rise diagram for each plumbing system.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/27/2022 ROBERT SHERRY WATER REVIEW Completed
06/28/2022 WBERGER1 ENGINEERING REVIEW Passed
06/28/2022 WBERGER1 ZONING REVIEW Approved
06/28/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/13/2022 JVINCEN1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/14/2022 VVERA1 OUT TO CUSTOMER Completed