06/07/2022 GSLEIGH1 OIP REVIEW Reqs Change Please see gas piping template, policy, and example on the Residential Permits information page:
https://www.tucsonaz.gov/pdsd/residential-permits

Provided drawings do not include project information - only one address on application but the drawing appears to be gas for two units. No lengths or appliance loads on the drawing. Lengths for pipe segments between every fitting (Change in diameter, elbow, or tee) must be provided as well as the fully developed length. All gas appliances must be indicated with their BTU load requirements to verify code compliance and safe delivery of gas to the home.

If more than one unit is affected by this work, please include updated address information in the narrative statement accompanying your revisions. Revisions must be submitted to existing application using the drop-down menu at the top of the online application form and entering activity number T22CM04162 where prompted.