Permit Number: T22CM04158
Parcel: 133060060

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM04158
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2022 RPARSON1 OIP REVIEW Completed
07/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04158

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
The standoff uplift capacity appears to be exceeded by the wind loads provided for roof 1. Please provide sufficient tilt leg standoffs for windloads. Revise and resubmit.


BUILDING REVIEW COMMENTS:
Approved
Addition of 10 solar modules to existing system with new inverter and changing to supply side tap from a back fed system


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Approved
Addition of 10 modules to exisiting PV system with a new supply side tap approved


PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/25/2022 NGARCIA3 OUT TO CUSTOMER Completed