Permit Number: T22CM04145
Parcel: 11107229D

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM04145
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2022 RPARSON1 OIP REVIEW Completed
07/14/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04145

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Sheet PV01 – Applicable codes using “2012” while 2018 IFC with City of Tucson applies. Provide applicable building codes.
Sheet PV01 – 2018 IRC sections referenced while 2018 IRC is not listed in applicable codes.
Sheet PV02 – Fire setbacks not shown on roof plan.
Sheet PV04 – Illegible signages. E.g. production meter graphics missing.


BUILDING REVIEW COMMENTS:
Denied
Sheet PV01 – Applicable codes using “2012” while 2018 IFC with City of Tucson applies. Provide applicable building codes.
Sheet PV01 – 2018 IRC sections referenced while 2018 IRC is not listed in applicable codes.
Sheet PV02 – Fire setbacks not shown on roof plan.
Sheet PV04 – Illegible signages. E.g. production meter graphics missing.


MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Denied
Sheet PV01 – Applicable codes using “2012” while 2018 IFC with City of Tucson applies. Provide applicable building codes.
Sheet PV01 – 2018 IRC sections referenced while 2018 IRC is not listed in applicable codes.
Sheet PV02 – Fire setbacks not shown on roof plan.
Sheet PV04 – Illegible signages. E.g. production meter graphics missing.



PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/14/2022 VVERA1 OUT TO CUSTOMER Completed