Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM04059
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/20/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Approv-Cond | Activity Number: T22CM04059 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Conditionally Approved THE RESPONSE TO THE FOLLOWING COMMENT SAYS: "WILL PROVIDE GEOTECHNICAL REPORT" WHICH IS NOT PROVIDED. THE INSPECTOR OF RECORD TO VERIFY GEOTECHNICAL REPORT PARAMETERS ARE SAME AS SHOWN ON STRUCTURAL DRAWINGS GENERAL NOTES SECTIONS AND ON THE STRRUCTURAL CALCULATIONS BEFORE APPROVAL. THE FOLLOWING COMMENT STAYS AND THIS PROJECT IS APPROVED WITH COMMENTS. 1. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1 BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Conditionally Approved Approved/subject to field approval ELECTRICAL REVIEW COMMENTS Conditionally Approval E101 POWER PLAN: Could not locate Key Notes 5, 9, 14, and 24. E102 LIGHTING PLAN: Should locate the Exit sign for door located between columns 1&2 and row B.7 to be closer vs current exit sign is a distance from door. PLUMBING REVIEW COMMENTS: Approved If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |