Permit Number: T22CM04059
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM04059
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM04059

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Sheet A701: The wall that separates this use with the adjacent tenant is required to be a fire wall. Section 503.1 states, "For the purposes of determining area limitations, height limitations and type of construction, each portion of a building separated by one or more fire walls complying with Section 706 shall be considered to be a separate building." Provide a properly rated rated wall in accordance with Section 503.1 and 706.
Response: The fire separation provided does not meet the minimum fire rating required for mercantile occupancies. The fire separation provided does not meet the vertical and horizontal continuity requirements for a firewall. This separation is required to be a fire wall in accordance with 706. Provide a fire wall in accordance with all the requirements of Section 706. Please follow all the applicable requirements in Section 706.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved


ELECTRICAL REVIEW COMMENTS
Conditionally Approved


PLUMBING REVIEW COMMENTS:
Approved



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
09/19/2022 STEVE SHIELDS ZONING REVIEW Approved