08/01/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04059

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
THE RESPONSE TO THE FOLLOWING COMMENT SAYS: "WILL PROVIDE GEOTECHNICAL REPORT" WHICH IS NOT PROVIDED.
THE INSPECTOR OF RECORD TO VERIFY GEOTECHNICAL REPORT PARAMETERS ARE SAME AS SHOWN ON STRUCTURAL DRAWINGS GENERAL NOTES SECTIONS AND ON THE STRRUCTURAL CALCULATIONS BEFORE APPROVAL. THE FOLLOWING COMMENT STAYS AND THIS PROJECT IS APPROVED WITH COMMENTS.
1. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1.


BUILDING REVIEW COMMENTS:
Denied
1. Sheet A101: Provide a section ramp that is in the rear of the store. This ramp must meet the requirements of Section 1012 to be considered an exit. Ramp section not provided.
2. Sheet A701: The wall that separates this use with the adjacent tenant is required to be a fire wall. Section 503.1 states, "For the purposes of determining area limitations, height limitations and type of construction, each portion of a building separated by one or more fire walls complying with Section 706 shall be considered to be a separate building." Provide a properly rated rated wall in accordance with Section 503.1 and 706.
Response: The fire separation provided is not properly rated. This separation is required to be a fire wall in accordance with 706. Provide a fire wall in accordance with all the requirements of Section 706.


MECHANICAL REVIEW COMMENTS:
Conditionally ApprovedAll corrections complied
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally ApprovedElectrical Review of Floor Décor
E101 POWER PLAN: Could not locate Key Notes 5, 9, 14, and 24.
E102 LIGHTING PLAN: Should locate the Exit sign for door located between columns 1&2 and row B.7 to be closer vs current exit sign is a distance from door.


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/03/2022 JVINCEN1 FIRE REVIEW Approved
08/09/2022 SSHIELD1 ENGINEERING REVIEW Passed
08/09/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM04059 – DP22-0111
7055 E Broadway Bl – C-2
TI - Retail (2nd Review)

TRANSMITTAL: August 9, 2022
This site is located in C-2 Zone (UDC 4.7.21), General Merchandise Sales is an allowed use in the zone (UDC Table 4.8-4) subject to Use Specific Standard 4.9.9.B.1.

1. Zoning has reviewed the building plans for compliance with DP22-0111 and although it appears that the building plans match the DP, Zoning cannot approve the building plan until the DP is approved.

2. This comment was not addressed. The development package sheets provided in the building set either need to be the stamped approved DP set, marked for reference only or removed from the building plan set.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.