Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM04054
Parcel: 136417010

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM04054
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/04/2022 RPARSON1 OIP REVIEW Completed
07/15/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04054

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide wind uplift calculations demonstrating pull out strength of individual connectors vs wind load factors.


BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/15/2022 VVERA1 OUT TO CUSTOMER Completed