Permit Number: T22CM03995
Parcel: 136061020

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM03995
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM03995
Addition
2127 S ROBERTO PL Zoning R-1

TRANSMITTAL DATE:?March ?29,2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: Provide a floor plan for the existing residence on the plan so that Zoning can verify if the requirements of UDC Article 4.9.7.B.7 are applicable to this project. Use Specific Standards 4.9.7.B.7 which states “ For any new single-family dwelling in the R-1 zone with five bedrooms , three parking spaces are required. For every bedroom over five, one additional space is required for each bedroom . For all single-family dwellings in the R-1 zone with five or more bedrooms , and for all lots containing two or more single-family dwellings, with the second dwelling having more than one bedroom , all parking spaces must be located on-site , either in a side or rear perimeter yard . Parking spaces may not be located in a vehicular use area in any front street perimeter yard . A parking area is not required to be developed to a commercial standard. A dustproof parking surface is required to at least a minimum of two inches of compacted pea gravel. An existing covered residential parking area may be used.



2.COMMENT: Draw dimension and label the height of the new structure measured from design grade to top of wall. Provide an average setback for the front of the garage and for the side of the proposed guest house

3.COMMENT: Please provide permit documentation for the existing art studio

4.COMMENT: For the proposed Sleeping quarters. Since this lot is located on a corner lot, the owner chooses which street lot line is the front lot line. From other than the front lot line , the street perimeter yard is ten feet. The required perimeter yard setback from the proposed sleeping quarters to the west property line is 10’-0”, proposed perimeter yard setback is 3‘7”.The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 10’-9” the required perimeter yard setback from the proposed accessory structure to the south property line is 7’- 3”, the proposed setback is 3’-0”. A Design Development Option (DDO) will need to be processed and approved to reduce the setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.

5.COMMENT: For the proposed Garage. Since this lot is located on a corner lot, the owner chooses which street lot line is the front lot line . From other than the front lot line , the street perimeter yard is ten feet, the front setback is 20’. The required perimeter yard setback from the proposed garage to the north property line is 20’-0”, proposed perimeter yard setback is 11’-7”. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 11’-4” the required perimeter yard setback from the proposed garage to the east property line is 7’ 7”, the proposed setback is 3’-11”. Based on a wall height of 11’-4” the required perimeter yard setback from the proposed garage expansion to the east property line is 7’-7”, the proposed setback is 1’-6”. A Design Development Option (DDO) will need to be processed and approved to reduce the setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.


If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
06/20/2022 PCAMARE1 ENGINEERING REVIEW Passed
06/20/2022 PCAMARE1 NPPO REVIEW Passed
06/20/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Update sheet #4 & 6 for consistancy with #13 & 17.
07/07/2022 JVINCEN1 FIRE REVIEW Approved