Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM03994
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM03994
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2022 LEVANS2 ENGINEERING REVIEW Reqs Change Combo permits cannot be approved until their associated development package has been approved.

Lianne Evans
lianne.evans@tucsonaz.gov
10/13/2022 PCAMARE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
10/13/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03994

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
All corrections complied
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E6.1 Electrical Panel Schedules: Comment only, NH1 & 2 don’t need 1000 amp buses


PLUMBING REVIEW COMMENTS:
Denied
Third Plumbing Review:
1 thru 4 OK
5). Now that plumbing plans have been included, they need to be accompanied by the civil plans for water service & sewer continuation as stated on plumbing pages. -IPC 106.3.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
10/13/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM03994 – Tucson Commerce Center
Building Plan Review (3rd Review)
3610 E Valencia Rd / I-1
TRANSMITTAL DATE:?October 13, 2022


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

2. COMMENT: Zoning has reviewed the building plans for compliance with the associated Development Package DP22-0100. Zoning cannot approve the building plans until the DP is approved.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov