Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2022 JVINCEN1 FIRE REVIEW Approved
07/23/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03994


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Denied
4. Provide ventilation calculations to all zones in an approved manner (IMC2018,403.3.1.1.1) Not Complied, you need to break it down into each occupancy classification as in table 403.3.1.1. you list the occupancy as lower level and upper level Not Complied
2. Provide a detailed narrative on the process that occurs in the warehouse (e.g. what materials are you storing in the warehouse, what type of forklifts are you using in the warehouse is it fuel or electric) (imc2018,106.3.1) Not Complied
3. You must submit mechanical plans for a mechanical review (IMC2018,106.3.1)


ELECTRICAL REVIEW COMMENTS
DeniedElectrical Review
No electrical plans submitted. Electrical permit is denied until code compliant plans are submitted.


PLUMBING REVIEW COMMENTS:
DeniedSecond Plumbing Review:
1 thru 3 OK
4). SAME-No Building drain or water stub ins or any plumbing plans shown on these plans? - IPC 301.3


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/27/2022 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: Iman Monshizadeh
PDSD Zoning Review Section

PROJECT: T22CM03994 – Tucson Commerce Center
Building Plan Review (2nd Review)
3610 E Valencia Rd / I-1

TRANSMITTAL DATE: July 27, 2022

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Zoning has reviewed the building plans for compliance with the associated Development Package DP22-0100. Zoning cannot approve the building plans until the DP is approved.


If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.Monshizadeh@tucsonaz.gov
08/09/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments
08/09/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review