Permit Number: T22CM03994
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM03994
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03994

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Structural Calculations are not stamped and signed by the design engineer in-charge, please provide the stamped and signed document for review.
2. In the structural Calculations and in the notes on drawing S1.0, frost depth is listed at 12 inches whereas the geotechnical report requires a minimum 24 inches with a 12 inch structural fill underneath extending 5 ft on each side of the footing.
3. Drawing S1.0 lists Seismic Design Category of the structure as “B” whereas an SDC of “C” is used in the structural calculations.
4. Seems like design of concrete tilt-up walls needs to be listed as a Deferred Submittal.
5. Footing Schedule on drawing S2.0 and S2.1 lists the depth of almost all footings less than Geotech recommended minimum two-foot depth. Footing depth needs to be revised as 4,000 psf design soil capacity used in the design is based on minimum 24 inches of footing depth.


BUILDING REVIEW COMMENTS:
Denied
1. Sheet A0.0: Remove the references to the Idaho State Plumbing Code.
2. Sheet A0.0: ESFR is not a sprinkler system type. It is a sprinkler head type. Provide the sprinkler system type being used. (NFPA 13)
3. Sheet A0.0: Why are frontage increases being applied if the building qualifies for unlimited area? Provide clarification and complete frontage increase calculations.


MECHANICAL REVIEW COMMENTS:
Denied
1.Provide ventilation calculations (IMC2018,,403.3.1.1.1) to show how you are going to meet the 4% openable area to the outdoors for natural ventilation
2. Provide a detailed narrative on the process that occurs in the warehouse (e.g. what materials are you storing in the warehouse, what type of forklifts are you using in the warehouse is it fuel or electric) (imc2018,106.3.1)


ELECTRICAL REVIEW COMMENTS
Denied
There are no electrical plans included to review. The submittal set calls out the electrical as a deferred submittal.
Electrical approval will be deferred until an electrical plan is submitted. If the contractor needs electrical approval before, will need to obtain approval from local AHJ.


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). Cover Sheet code summary is calling out 2017 Idaho Plumbing Code? Should be 2018 International Plumbing Code
2), Add Gutter & downspout sizing calculations to plan page A2.5 -IPC 1106.1, 1106.3, 1106.6
3). Add a Downspout grade level connection detail to plan page A2.5 - IPC 1101.6
4). No Building drain or water stub ins shown on these plans? - IPC 301.3



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/16/2022 ROBERT SHERRY WATER REVIEW Passed
06/21/2022 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh
PDSD Zoning Review Section

PROJECT: T22CM03994 – Tucson Commerce Center
Building Plan Review (1st Review)
3610 E Valencia Rd / I-1

TRANSMITTAL DATE: 6/21/2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: Zoning has reviewed the building plans for compliance with the associated Development Package DP22-0100. Zoning cannot approve the building plans until the DP is approved.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the Development Package.

3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.

If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.Monshizadeh@tucsonaz.gov
06/21/2022 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change Impact fees will be assessed when zoning review is complete.
06/28/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments
07/07/2022 JVINCEN1 FIRE REVIEW Reqs Change See building comments

john.vincent@tucsonaz.gov
5203495581

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2022 VVERA1 OUT TO CUSTOMER Completed