Permit Number: T22CM03914
Parcel: 118020490

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM03914
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2022 IMONSHI1 ZONING REVIEW Approved
06/07/2022 IMONSHI1 NPPO REVIEW Passed
06/16/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03914

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Clarify if the garage door header is existing and is to remain once the wall infill is removed or if a new header will be installed. If a new header is required, indicate its size on the framing plan.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied
1. Note that all new or replaced 15- and 20-amp outlets shall be tamper proof type. 2017 NEC 210.52.
2. Note that the new receptacles in the garage will be GFCI protected. 2018 IRC E3902.2.
3. Clarify if the area in the garage next to the sink is to be a work counter and would require outlets to be installed in accordance with 2018 IRC E3901.4. This area is shown empty on the dimensioned floor plan sheet A1.0 however appears like a built in counter on the electrical plan.


PLUMBING REVIEW COMMENTS:
Denied
1. Note on the drawings that all plumbing drain, waste and vent systems shall be tested for leaks in accordance with the 2018 IRC P2503.5 prior to concealing.
2. Indicate all hot water lines will be insulated to a minimum of R3 2018 IRC N1103.4.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/28/2022 SSHIELD1 ENGINEERING REVIEW Passed