Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM03904
Parcel: 11011374D

Address:
4857 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM03904
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM03904 – DP22-0114
4857 E Grant Rd – C-2
Food Service – Shell Building (1st Review)

TRANSMITTAL: June 21, 2022
This site is located in C-2 Zone (UDC 4.7.21), Auto Repair Major use is an allowed use in the zone (UDC Table 4.8-4) subject to Use Specific Standard 4.9.13.E.

1. Zoning has reviewed the building plans for compliance with DP22-0114 and although it appears that the building plans match the DP, Zoning cannot approve the building plan until the DP is approved. As changes to the DP are required changes to the architectural site plan maybe required.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/16/2022 JPEELDA1 FIRE REVIEW Reqs Change Devlopment plan review remarks shall be addressed for fire sprinkler requirements prior to CM being approved by TFD.
Notes shall also state:
Seperate submittals for kicthen fire suppression system
Bulk CO2 system alarm permit required from TFD

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
08/16/2022 DBENOIT1 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM03904

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.

BUILDING REVIEW COMMENTS:
N/A


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved for Core and Shell only, plans tenant buildout will be submitted on a later date


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
N/A



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
09/07/2022 SBLOOD1 ENGINEERING REVIEW Approved