Permit Number: T22CM03902
Parcel: 11011374D

Address:
4857 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM03902
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03902


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
All sheets – Provide correct project address for construction documents. Permit application states “4857” Grant Rd. While Architectural sheets show “TBD.” “4800” shown in Structural, Mechanical, Plumbing, Electrical, COMcheck, and Structural Calculations. What is the project site address?


BUILDING REVIEW COMMENTS:
Denied
All sheets – Provide correct project address for construction documents. Permit application states “4857” Grant Rd. While Architectural sheets show “TBD.” “4800” shown in Structural, Mechanical, Plumbing, Electrical, COMcheck, and Structural Calculations. What is the project site address?
Life Safety Plan – Egress life safety plan missing. Show exit travel distance, common path of travel, portable extinguisher locations, and exit signs. Egress shall not pass-through kitchen or spaces used for similar purposes per 2018 IBC 1016.2 while office occupant is passing through “BACK KITCHEN.”
Sheet G000 – List the all the applicable building codes per City of Tucson requirements.
City of Tucson IBC Local Amendments
• Amendments to the 2018 International Building Code
• Amendments to the 2018 International Energy Conservation Code
• Amendments to the 2018 International Fuel Gas Code
• Amendments to the 2018 International Mechanical Code
• Amendments to the 2018 International Plumbing Code
• Amendments to the 2017 National Electrical Code
• Amendments to the 2018 International Fire Code
• City of Tucson/Pima County Outdoor Lighting Code
• ICC A117.1 - 2009 Accessible and Usable Buildings and Facilities (by reference)


MECHANICAL REVIEW COMMENTS:
Denied
All sheets – Provide correct project address for construction documents. Permit application states “4857” Grant Rd. While Architectural sheets show “TBD.” “4800” shown in Structural, Mechanical, Plumbing, Electrical, COMcheck, and Structural Calculations. What is the project site address?


ELECTRICAL REVIEW COMMENTS
Denied
All sheets – Provide correct project address for construction documents. Permit application states “4857” Grant Rd. While Architectural sheets show “TBD.” “4800” shown in Structural, Mechanical, Plumbing, Electrical, COMcheck, and Structural Calculations. What is the project site address?
Sheet E115 – Show undergrounded conductors colors per City of Tucson Amendment to the 2017 National Electrical Code per section 210.5.


PLUMBING REVIEW COMMENTS:
Denied
All sheets – Provide correct project address for construction documents. Permit application states “4857” Grant Rd. While Architectural sheets show “TBD.” “4800” shown in Structural, Mechanical, Plumbing, Electrical, COMcheck, and Structural Calculations. What is the project site address?


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/15/2022 ROBERT SHERRY WATER REVIEW Completed
06/21/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments
06/21/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM03902 – DP22-0114
4857 E Grant Rd – C-2
TI – Food Service (1st Review)

TRANSMITTAL: June 21, 2022
This site is located in C-2 Zone (UDC 4.7.21), Auto Repair Major use is an allowed use in the zone (UDC Table 4.8-4) subject to Use Specific Standard 4.9.13.E.

1. The architectural site plan provided in the building plan set does not match DP22-0114.

2. The architectural site plan shows outdoor seating that does not appear to be shown on DP22-0114, coordinate with the civil engineer to ensure that the outdoor seating ins included on the DP.

3. Zoning has reviewed the building plans for compliance with DP22-0114 and although it appears that the building plans match the DP, except for the comments above, Zoning cannot approve the building plan until the DP is approved.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
06/21/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/06/2022 JVINCEN1 FIRE REVIEW Reqs Change See building comments

john.vincent@tucsonaz.gov
5203495581

Final Status

Task End Date Reviewer's Name Type of Review Description
07/06/2022 NGARCIA3 OUT TO CUSTOMER Completed