Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM03867
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/08/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/13/2022 | JPEELDA1 | FIRE | REVIEW | Approved | |
06/13/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, 504.4, 504.6, and 504.8.6, IMC 2018. 2. Show how the dryer installation complies with Section 504.6, IMC 2018 for make-up air. |
06/13/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Detail 4/P1.0 calls for the drain from the pan under the water heater to be capped. The drain shall not be capped but shall terminate either to an indirect waste receptor or to the exterior of the building. The tailpiece of a fixture is not an approved indirect waste receptor. Reference: Sections 504.7.2 and 802.4, IPC 2018. 2. Show the location of the location of the full-open valve for the water supply entrance to each dwelling unit (unless each fixture is equipped with stop valves). Reference: Section 606.1(6), IPC 2018. |
06/20/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/20/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |