Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM03867
Parcel: 11626273E

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM03867
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/13/2022 JPEELDA1 FIRE REVIEW Approved
06/13/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, 504.4, 504.6, and 504.8.6, IMC 2018.
2. Show how the dryer installation complies with Section 504.6, IMC 2018 for make-up air.
06/13/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Detail 4/P1.0 calls for the drain from the pan under the water heater to be capped. The drain shall not be capped but shall terminate either to an indirect waste receptor or to the exterior of the building. The tailpiece of a fixture is not an approved indirect waste receptor. Reference: Sections 504.7.2 and 802.4, IPC 2018.
2. Show the location of the location of the full-open valve for the water supply entrance to each dwelling unit (unless each fixture is equipped with stop valves). Reference: Section 606.1(6), IPC 2018.
06/20/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/20/2022 NGARCIA3 OUT TO CUSTOMER Completed