Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM03862
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/22/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Verify that the specified make-up air unit is equipped with a water reuse or recycling system. Evaporative cooling systems that do not include water recycling or reuse systems are prohibited by the Arizona Revised Statues, ARS 45-313. [Initial comment: Provide a mechanical design for the proposed changes to the kitchen that clearly shows that the changes will comply with the requirements of Sections 302, 304, 506, 507, and 508, IMC 2018. Reference: Section 107.2.1, IBC 2018.] |
| 08/22/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | There is insufficient information to review the modifications to the existing natural gas distribution system. Provide a natural gas piping design, including the piping layout on a floor plan and a natural gas schematic showing the sizes, loads and developed lengths of the piping for the entire system. Reference: Section 107.2.1, IBC 2018. [Initial comment: Provide plumbing plans for the demolition and the new work, including water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2018.] |
| 08/29/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |