Permit Number: T22CM03839
Parcel: 132130730

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM03839
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Per the last plan comment, entered on 7-13-22 as follows,

(1. Ref; Plan Sheet SE-1 Site Plan.

(a) Provide an additional site lighting plan without the photometrics, showing all existing lighting including New Proposed Lighting, identifying all luminaires with an identifying mark that correlates with the provided lumen table and luminaire schedule. The over- laying photometrics makes it impossible to clearly identify each luminaire. OLC section 102.4.2.)

(b) The new submitted site plan does not show existing luminaires ‘B’, ‘F’, and ‘F1’, as accounted for in the Table on plan sheet SE-1. Please revise the site lighting plan to reflect this.

Please include manufacture cut sheets in with the plan set.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC)
08/08/2022 STEVE SHIELDS ZONING REVIEW Reqs Change Unitl DP21-0214 has been approved Zoning cannot approve this plan.