Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM03839
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/04/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Per the last plan comment, entered on 7-13-22 as follows, (1. Ref; Plan Sheet SE-1 Site Plan. (a) Provide an additional site lighting plan without the photometrics, showing all existing lighting including New Proposed Lighting, identifying all luminaires with an identifying mark that correlates with the provided lumen table and luminaire schedule. The over- laying photometrics makes it impossible to clearly identify each luminaire. OLC section 102.4.2.) (b) The new submitted site plan does not show existing luminaires ‘B’, ‘F’, and ‘F1’, as accounted for in the Table on plan sheet SE-1. Please revise the site lighting plan to reflect this. Please include manufacture cut sheets in with the plan set. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC) |
| 08/08/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | Unitl DP21-0214 has been approved Zoning cannot approve this plan. |