Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T22CM03839
Parcel: 132130730

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM03839
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2022 STEVE SHIELDS ZONING REVIEW Reqs Change Unitl DP21-0214 has been approved Zoning cannot approve this plan.
07/13/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Ref; Plan Sheet SE-1 Site Plan.

(a) Provide an additional site lighting plan without the photometrics, showing all existing lighting including New Proposed Lighting, identifying all luminaires with an identifying mark that correlates with the provided lumen table and luminaire schedule. The over- laying photometrics makes it impossible to clearly identify each luminaire. OLC section 102.4.2.

(b) Verify that there are no unshielded luminaires (existing or new) as stated in the lumen table.

(C) Provide manufacture cut sheets to verify Shielding and lamp color compliance or use the exception. Section 104.2 (1)(2).

Be advised, the special inspectors are experts in this field and are very detail oriented.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC)