Permit Number: T22CM03839
Parcel: 132130730

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM03839
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/20/2022 SSHIELD1 ENGINEERING REVIEW Passed
05/23/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Provide reference to the 2012 Tucson/Pima County Outdoor Lighting Code (OLC), not "OUTDOOR ENERGY CODE". Include lighting area as well as option Table 401.1.

2. The outdoor lumen calculations must include all exterior lighting on the site. Existing also. OLC 104.2.1(1),(2),(3).

3. Verify compliance OLC section 102.4.

4. Verify compliance with OLC section 402.1.

5. Indicate whether a special inspection is required or not. OLC section 104.2.2, 106.2.

6. Provide complete compliance with the 2018 IECC for the exterior lighting.

7. The site of the parcel shown on the lumen calculations does not correlate with the site plan SD101 or Pima County GIS of 14.35 acres. Please clarify.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC).
05/23/2022 STEVE SHIELDS ZONING REVIEW Reqs Change Unitl DP21-0214 has been approved Zoning cannot approve this plan.
05/24/2022 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/24/2022 VVERA1 OUT TO CUSTOMER Completed