Parcel: 13003018E

Address:
2540 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM03804
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 1 of 8: The previous C of O was for a church, so Adult Day Care will be a change of use. You must provide a site plan (you can use Sheet A-1). You must provide a Floor Plan (do not use the 'As-Builts' plan on Sheet A-2). Create a new plan, removing the red clouds and notes. Instead, indicate numbered plan notes with numbers on the plan for new walls, walls to be removed, door changes, etc.).
2. Sheet L-1: Remove this sheet.
3. Sheet A-1; Site Plan: Indicate the handicap parking and striping on this sheet.
4. Sheet A-1; Code Notes: For the new C of O, revise these notes to serve as the Code Analysis. Indicate the Occupancy Classification (IBC Chapter 3), the Total Building SF, the Building Construction Type (IBC Chapter 6), and the Building Occupant Load (IBC Table 1004.5. In addition, list all Applicable Codes for this project.
5. General: The C of O Application indicated the Type of Business as an 'Adult Day Care', and the Business Description indicated 'Assembly (Performing arts, self-defense, independent skills/supports, etc.). Please clarify.
6. General: Seal, sign, and date all drawings by the registered design professional.
7. General: Please provide a reasonable project valuation for the work to be performed for this permit. $100 was indicated in the Application.
8. General: Please provide written responses to all review comments.
05/25/2022 JPEELDA1 FIRE REVIEW Reqs Change I-4 shall have fire sprinklers installed in buildings that do not have a door in every room where care is provided has not fewer than one exit. IFC 2018, Chapter 9, Section 903.2.6. The plans do not show rooms where care is given. We will need a more detailed plan. If areas where care is given do not have an access door fire sprinklers shall be installed throughout the facility.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@tucsonaz.gov
520-837-7033Fire Plans Examiner
06/02/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. This activity is a change of use. Provide new drawings.
2. Calculate the number of required plumbing fixtures for the building based on the new occupancy. Reference: Section 2902.1, IBC 2018.
06/02/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. This activity is a change of use. Provide new drawings.
2. Provide calculations to verify that adequate ventilation will be provided for the new occupancy in the space. Reference: Section 403.3.1.1, IMC 2018.
06/02/2022 ROBERT SHERRY WATER REVIEW Reqs Change 1. This activity is a change of use. Provide new drawings.
2. Provide the size and location of the water meter and its backflow preventer.
06/13/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.
1. Provide complete electrical plans for all changes required to accomadate the new use of the building. Plans must be sealed by an Arizona Registrant.
2. Provide compliance with the 2017 NEC, 2018 IECC, and 2012 Tucson/Pima County Outdoor Lighting Code.
Ref: 2018 IBC section 107.2.1
06/16/2022 SSHIELD1 ENGINEERING REVIEW Passed
06/16/2022 STEVE SHIELDS ZONING REVIEW Approved
06/16/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed