Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM03799
Parcel: 134244300

Address:
6363 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM03799
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/25/2022 WBERGER1 ZONING REVIEW Approved
08/01/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM03799

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
1. Architectural and S-drawing shows a new mezzanine floor, structural design calculations for the mezzanine floor framing and its associated foundations is not provided. Please provide the same for lateral (earthquake) and gravity loads.- Structural calculations not provided for the mezzanine. Review for mezzanine is INCOMPLETE as a complete review could not be provided. If applicant wants a complete review provide the requested information otherwise this review is approved CONDITIONALLY that mezzanine is not part of this review.
2. Please provide structural design details and calculations for the anchorage of racks and for the installation of the proposed acoustical ceilings. - Please list this item as a Deferred ITEM.
3. Provide design for the anchorage of the roof-top mechanical units and adequacy of the existing roof framing members supporting those units for the design wind loads - resolved


BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/03/2022 JVINCEN1 FIRE REVIEW Reqs Change The exit signs in-between the M and S are still on sheet E1.0. The exits from the M cannot be through a storage room as indicated on previous comments.

john.vincent@tucsonaz.gov
5203495581
08/10/2022 SCABRAL1 ENGINEERING REVIEW Passed