Permit Number: T22CM03773
Parcel: 125076370

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM03773
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/19/2022 WBERGER1 ENGINEERING REVIEW Passed
05/19/2022 WBERGER1 ZONING REVIEW Approved
05/31/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/01/2022 JPEELDA1 FIRE REVIEW Approved
06/07/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/07/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The cooling load calculations for the space show a total coil load of 32.8 MBH to be covered by FC-1 (existing, 2-tons) plus FC-2, but the specification for the new FC-2 calls for a total capacity of 32.9 MBH. In addition, the COMcheck Mechanical Compliance shows only one unit to serve the space. How does this comply with the requirements of Section C403.3.1, IECC 2018?
06/07/2022 ROBERT SHERRY WATER REVIEW Completed
06/14/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Show location and provide power and disconnect for new FC #2 and EF#1 on the power floor plan and correlate with the panel schedule. See Mechanical plan.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.