Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/19/2022 | WBERGER1 | ZONING | REVIEW | Approved | |
05/19/2022 | WBERGER1 | ENGINEERING | REVIEW | Passed | |
05/19/2022 | WBERGER1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/31/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/01/2022 | JPEELDA1 | FIRE | REVIEW | Approved | |
06/07/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
06/07/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The cooling load calculations for the space show a total coil load of 32.8 MBH to be covered by FC-1 (existing, 2-tons) plus FC-2, but the specification for the new FC-2 calls for a total capacity of 32.9 MBH. In addition, the COMcheck Mechanical Compliance shows only one unit to serve the space. How does this comply with the requirements of Section C403.3.1, IECC 2018? |
06/07/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
06/14/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Show location and provide power and disconnect for new FC #2 and EF#1 on the power floor plan and correlate with the panel schedule. See Mechanical plan. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |