Permit Number: T22CM03770
Parcel: 129020870

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM03770
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Is the Sign part of the proposed scope of work? If not, Indicate this on the plan. If yes, apply for a Sign Review and permit.

2. Provide compliance with the 2018 IECC for the lighting.

3. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. See section 104 for required information needed on the plans to provide evidence that the unshielded border lighting complies with the lumen cap allowed per acre and lamp output color temperature restrictions.

4. Provide a complete electrical plan sealed by a Registrant registered in the State of Arizona.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC).

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2022 NGARCIA3 OUT TO CUSTOMER Completed