Permit Number: T22CM03764
Parcel: 130102830

Address:
3126 E 29TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM03764
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2022 WBERGER1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Wyatt Berger
Planner

PROJECT: T22CM03764
3126 E 29th St
Enclose carport and porch into family room, study, and two bathrooms (1st Review)

TRANSMITTAL DATE: May 18, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Include the square footage of all accessory structures on the site on the title sheet.
2. Provide a lot coverage calculation for the property. Lot coverage includes the area occupied by buildings, outdoor storage areas, and driveways (both paved and unpaved).
3. The accessory structure near the southeast corner of the lot appears in aerial photography beginning in 2005. Either provide permit documentation for this accessory structure or include this structure within your scope of work. A Design Development Option (DDO) (UDC 3.11) may be required if the structure is not meeting setback requirements, and if there is no permit documentation available. Contact Mark Castro at Mark.Castro@tucsonaz.gov for more information regarding the DDO process.
4. The latest aerial photography shows a detached accessory structure at the front of the property. Per UDC 6.6.3.C, detached accessory structures are not permitted in the buildable area extending the full width of the lot between the principal building and the front street lot line. A Board of Adjustment variance is required for the detached accessory structure to remain. Contact Mark Castro at Mark.Castro@tucsonaz.gov for further information regarding the variance process. Either remove this structure or pursue the variance process.

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or 520-837-4951.
05/18/2022 WBERGER1 ENGINEERING REVIEW Passed
06/02/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM03764


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide the existing structural framing of the car port and changes that will be made.
2. Provide any framing drawings required.


BUILDING REVIEW COMMENTS:
Denied
1. The applicable and adopted codes are missing from the title sheet. Include this list of codes on the title sheet.
2. Provide an existing layout and demo layout.
3. Provide all new elevations for the new layout.
4. Note on the drawings that fire blocking will be installed in all walls and concealed spaces where newly built or existing areas in which the framing is exposed during construction. 2018 IRC R302.11.


MECHANICAL REVIEW COMMENTS:
Denied
1. Note on the drawings that all bath fans will be exhausted directly to the exterior. 2018 IRC M1505.2.
2. Note that ducts, air handlers and filter boxes shall be sealed. 2018 IRC M1601.4.1.
3. Note on the drawings that the ducts will be tested for air leakage in accordance with 2018 IECC R4503 unless they are installed within conditioned space.
4. Note on the drawings that the new ductwork will be insulated to a minimum of R8 if not installed within conditioned space. 2018 IECC R403.3


ELECTRICAL REVIEW COMMENTS
Denied
1. Note on the drawings that smoke detectors and carbon monoxide detectors will be installed in the existing dwelling, not just the new bedroom. The location of these detectors will be verified during inspection. 2018 IRC R314.2.
2. Note on the drawings that all smoke detectors shall be interconnected so that the actuation of one alarm will activate all. 2018 IRC R314.4.
3. Note on the drawings that the smoke alarm devices will receive their primary power from the building wiring with a battery backup. 2018 IRC R314.4.6.
4. Note that all new or replaced 15- and 20-amp outlets shall be tamper proof type. 2017 NEC 210.52.


PLUMBING REVIEW COMMENTS:
Denied
1. Clarify if the existing water service and water meter is of sufficient size to accept the new plumbing load.
2. Note on the drawings that all plumbing fixtures shall be low flow type. Toilets are required to be low flush using 1.6 gallons per flush or less, while showerheads and faucets must not exceed 2.5 gallons a minute. Ordinance 7178.
3. Note on the drawings that all plumbing drain, waste and vent systems shall be tested for leaks in accordance with the 2018 IRC P2503.5 prior to concealing.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/18/2022 WBERGER1 NPPO REVIEW Passed