Permit Number: T22CM03760
Parcel: 131032210

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM03760
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2022 WBERGER1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Wyatt Berger
Planner

PROJECT: T22CM03760
1718 S Beverly Av
Front porch addition (1st Review)

TRANSMITTAL DATE: May 18, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Provide a residential plot plan that meets all the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. At a minimum, this plan shall:
a. Be drawn at an engineering scale.
b. Show the square footage of the lot, existing dwelling, proposed addition, accessory structures, and total under roof area.
c. Provide a lot coverage calculation. Lot coverage includes the area of the site occupied by buildings, storage areas, and driveways (paved and unpaved).
d. Provide the height of the exterior walls of the proposed project.
e. Show all street perimeter setbacks measured from the proposed project to the property as well as to the centerline of each street.

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or 520-837-4951.
05/18/2022 WBERGER1 NPPO REVIEW Passed
06/09/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM03760
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.
Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits
SITE PLAN:
1. Indicate the location of buildings and any utilities supporting or effecting the proposed structure.

FOUNDATION PLAN:
1. Dimension the footing length, width, and depth into undisturbed soil for each footing type and condition, R403.1. Show the minimum 12” reinforced footing depth below the undisturbed ground surface R403.1. Show rebar reinforcement with 3” clearance from earth, R403.1.3.5.3. Provide ½” anchor bolts with 7” embedment, R403.1.6.

SECTIONS - DETAILS:
1. Show the Post Section Detail with #4 rebar in the footing, R403.1.
2. Notate and specify the size of post base with 1” standoff above concrete, R317.1.4 exception 1.
3. Show roof (uplift resistance) rafter fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.
4. Show connection at dwelling with fasteners (rafter on top plate with H2.5 or ledger connection to load bearing wall).

ELECTRICAL PLANS:
1. Show the overhead service conductor with an 8-foot clearance above the roof, E3604.2.1 or relocate the service panel from under the roof. The service line change or a new panel location must be coordinated with TEP for approval.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
520 837-4912
City of Tucson Residential Plan Review
06/27/2022 PCAMARE1 ENGINEERING REVIEW Passed